  • MDR-60 is a slim line DIN rail Class I switching power supply.
  • Designed with a fully insulated plastic housing to prevent user contact and risk of electric shock.
  • With efficiency up to 88%, this series can be cooled using only free air convection up to 60°C, significantly increasing the reliability and lifespan of the power supply.
  • Other standard features include low no-load power consumption to save energy, short circuit, overload and over voltage protections, and DC OK relay contact with LED indicator to monitor power supply status.
Industria / F. de alimentación
  • DC
    DC
  • Interfaz
    Interfaz

Specifications

Model specification MDR-60-5 MDR-60-12 MDR-60-24 MDR-60-48
Production DC voltage 5V 12V 24V 48V
Nominal current 10 A 5A 2.5A 1.25A
Current scope 0 ~ 10A 0 ~ 5A 0-2.5A 0-1.25A
Nominal power 50W 60W 60W 60W
Ripple and noise (max.) 80mVp-p 120mVp-p 150mVp-p 200mVp-p
Voltage adjustment range 5-6V 12-15V 24-30V 48~56V
Voltage tolerance ±2,0% ±1,0% ±1,0% ±1,0%
Line regulation ±1,0% ±1,0% ±1,0% ±1,0%
Load regulation ±1,5% ±1,0% ±1,0% ±1,0%
Configuration, rise time Note.5 500 ms, 30 ms/230 VCA
500 ms, 30 ms/115 VCA
a carga completa
Waiting time (typ.) 50 ms/230 VCA
20 ms/115 VCA
a plena carga
Input Voltage range 85~264 VCA
120~370 VCC
Frequency range 47~63Hz
Efficiency (typ.) 78% 86% 88% 87%
AC current (typical) 1.8A/115VCA
1A/230VCA
Inrush current (typical) COLD START:
30A/115VAC
60A/230VAC
Leakage current <1mA/240VCA
Protection Overload 105%~150% rated output power
Protection Type: Constant current limiting, automatically recovers after fault condition is removed
surge 6.25-7.25 V 15,6-18V 31.2-36V 57.6 - 64.8 V
Protection type: Turn off the output voltage, turn it back on to recover
Function CC signal Relay Contact Rating (Max): 30V/1A Resistive



Environment Working humidity 20% ~ 90%RH non-condensing
Storage Temperature Humidity -40°C ~ +85°C, 10% ~ 95% HR
Temperature coefficient ±0,03%/°C (0 – 50°C)
Vibration Component: 10 – 500 Hz, 2G 10 min./1 cycle, the period of 60 min. each along X, Y and Z axes; Mounting: Compliance with IEC60068-2-6
Safety and electromagnetic compatibility Safety standards Approved by UL508, UL60950-1, TUV EN60950-1
Withstand voltage l/P-0/P: 3KVCA
l/P-FG:2KVCA
0/P-FG: 0,5KVCA
Insulation resistance l/PO/P, l/P-FG, 0/P-FG:>100 M ohmios/500 V CC/25 °C/70 % HR
CEM emission Compliance with EN55011, EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
EMC immunity Compliance with EN6100 (M-2, 3, 4, 5, 6, 8,11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criterion A
Others MTBF 299.2K hours min. MIL-HDBK-217F (25°C)
Dimension 40*90*100mm(WxHxD)
Packaging 0.33 kilograms; 60 pieces/20 kg/0.82 square feet.
Use 1. All parameters NOT specifically mentioned are measured at 230VAC input, rated load and 25°C ambient temperature.
2. Ripple and noise are measured at 20MHz bandwidth using a 12″ twisted pair cable terminated with a 0.1 and 47uf parallel capacitor.
3. Tolerance: includes configuration tolerance, line regulation and load regulation.
4. The power supply is considered a component that will be installed in the final equipment. It must be reconfirmed that the final equipment still complies with the EMC directives. For guidance on how to perform these EMC tests, see "EMI Testing of Component Power Supplies".
5. Setup time duration is measured at first cold start. Turning the power supply on/off may cause an increase in setup time.